EVCO EPK4BHQ1AH Installer manual User Manual
Page 31

EVCO S.p.A.
c-pro 3
NODE kilo AHU | Application manual ver. 1.0
page 31 of 114
PU19
Neutral
zone
management
winter
dehumidification
6
0
100
%
IS-U
PU20
Differential
management
winter
dehumidification
10
0
100
%
IS-U
PU21
Integral
time
management
winter
dehumidification
0
0
999
Sec
IS-U
If
PU04 = 0
integral
action
Is not
present
PU22
Set-point maximum aperture winter
Dehumidification
50.00
0.00
100.00
%
IS-U
PU23
Maximum differential opening winter
Dehumidification
20.00
0.00
100.00
%
IS-U
PU24
Type winter dehumidification:
0: only dehumidifies winter
1: only adjustment
2: larger of the two
3: average of the two
0
0
3
-
IS-U
DAMPERS
PS01
Type of Free-Cooling / Free-Heating
0: Disabled
1: Free-Cooling / Free-Heating in
temperature
1
0
1
-
IS-SE
PS03
Damper command type
0: Only for Free-Cooling/Free-Heating
1: Only for controlling air quality
2: Priority to the greater of the two
requests
3: Average of the two requests
4: Fixed opening
0
0
4
-
IS-SE
PS05
Minimum opening for the dampers
20.0
0.0
PS06
%
IS-SE
PS06
Maximum opening for the dampers
100.0
PS05
100.0
%
IS-SE
PS07
Pre-start time
45
0
65535
Sec
IS-SE
PS08
Switch-off delay
15
0
999
Sec
IS-SE
PS09
End run time
30
0
999
Sec
IS-SE
PS10
Fixed value for opening dampers
50.0
0.0
100.0
%
IS-SE
PS12
Differential enabling free-cooling and
free-heating in temperature
2.0
0.0
20.0
°C
IS-SE
PS13
Differential Set Point enabling free-
cooling and free-heating in temperature
4.0
0.0
20.0
°C
IS-SE
PS15
Minimum and maximum opening of
dampers
0: Disabled
1: Only inside band
2: Always
2
0
2
-
IS-SE
PS20:
Set Point – Air Quality Control
600
0
10000
ppm
IS-SE