WINTER operation/HEATING: Free-Heating

Note: if one of the sensors included in the control is in error the control of the free-cooling/free-heating can no longer

be utilized and the heating/cooling ramp regulate the total control differential.

6.16.5

Air quality control

The outdoor damper may be used to replace the air upon request by the appropriate sensor (VOC/CO2). It is

necessary to enable the parameter PS02=1, and the control sensor for the air quality (PH46>0). The outdoor dampers

can be commanded based on the control sensor at set point (PS20) and at the relative differential (PS21).

Note: If the air quality sensor is in error the control is inhibited. The sensor can be one of three types: 4..20mA

(PH46=1), 0..5V (PH46=2) or 0..10V (PH46=3);

Note: the air quality sensor is always connected on the AI3 remote.

6.16.6

Damper command

The outdoor damper can be utilized for two controls: free-cooling/free-heating and air quality control.

The priority of these requests is decided by parameter PS03:

-

PS03=0: The shutter is commanded by Free-cooling / Free-heating

-

PS03=1: The shutter is commanded by air quality control

-

PS03=2: The shutter is commanded by the largest request

-

PS03=3: The damper request is calculated as the arithmetic mean of the two free-cooling (/free-heating)

and air quality control requests. In a way to satisfy both active requests.

-

In order to correctly command the external shutter motor it is necessary to set the following parameters:

-

PS05. Minimum position of dampers.

-

PS06. Maximum position of dampers.

-

PS07. Damper run time to go from 0% to 100%.

-

PS08. Maximum time to maintain signal at end of relay.

-

PS09 (optional). If greater than zero the command at relay are given only when the actual variation on the

control ramp exceeds the set value. If PS09=0 the command will always pass.

-

PS15 The minimum opening of damper can be deactivated (PS15=0), limited only if regulation is active

(PS15=1), or always active (PS15=2).

Set Point

Supply

T. Supply

Pb01

Pb01 /

NZ

Pb03

100 %

0 %

Heating coil

Outdoor air dampers
regulated in free-heating