EVCO S.p.A.

c-pro 3

NODE kilo AHU | Application manual ver. 1.0

page 29 of 114

PF17

Max. temperature of limitation

40.0

-15.0

70.0

°C

IS-F

PF18

Differentials for fan limitation

5.0

0.0

30.0

°C

IS-F

PF19

Air Quality regulation min set point

500

0

10000

ppm

IS-F

PF01=4

PF01=5

PF20

Air Quality regulation max set point

1100

0

10000

ppm

IS-F

PF01=4

PF01=5

PF21

Value of first modulating step

33.0

0.0

PF22

%

IS-F

PF22

Value of second modulating step

66.0

PF21

PF23

%

IS-F

PF23

Value of third modulating step

100.0

PF22

100.0

%

IS-F

PF24

Fans speed change time

2

0

999

sec

IS-F

PF25

Fans switch-on minimum time

60

0

999

sec

IS-F

PF26

Enable post-ventilation

1 (Yes)

0 (No)

1 (Yes)

IS-F

PF27

Fans time in post-ventilation

30

0

999

sec

IS-F

PF28

Return fan percentage delta

0.0

-100.00

100.00

%

IS-F

PF29

Return fan step delta

0

-2

2

step

IS-F

HEATING-COOLING COILS

Pb01

Proportional band for control of valves

(cooling/heating)

10.0

0.0

20.0

°C

IS-B

Pb02

Integral time for control of valves

(cooling/heating)

0

0

999

Sec

IS-B

If

Pb02=0

integral

action

not

present

Pb03

Neutral zone temperature control

4.0

0.0

20.0

°C

IS-B

Pb05

Maximum

shifting

for

Set

Point

calculation running of return

0.0

0.0

20.0

°C

IS-B

If

Pb05=0

function

not

enabled

Pb06

Proportional band for the Set Point

calculation running of return

5.0

0.0

20.0

°C

IS-B

Pb10

Opening of heating valves alarm sensor

return

30.0

0.0

100.0

%

IS-B

Pb11

Opening of cooling valves alarm sensor

return

30.0

0.0

100.0

%

IS-B

Pb15

Priority of cooling request

0: Cooling

1: Dehumidification

2: Highest

3: Medium

0

0

3

IS-B

Pb20

Insertion/release time single stage of

heating element for the post-heating

60

0

999

Sec

IS-B

Pb21

Second entire neutral area for heat in

the case of 2 hot coils

12.0

0.0

20.0

°C

IS-B

Pb22

Second differential in the case of 2 hot

coils

3.0

0.0

10.0

°C

IS-B

Pb23

Neutral zone for midseason control

12.0

0.0

20.0

°C

IS-B