EVCO EPK4BHQ1AH Installer manual User Manual
Page 33

EVCO S.p.A.
c-pro 3
NODE kilo AHU | Application manual ver. 1.0
page 33 of 114
PA21
Pressure switch alarm delay (heat
recovery device)
30
0
999
Sec
IS-S
PA22
Type of general alarm reset
0: Auto - Automatic
1: Manu - Manual
Manu
(1)
Auto
(0)
Manu
(1)
-
IS-S
PA23
General alarm delay
30
0
999
Sec
IS-S
PA24
Type of alarm re-arm pressure switch
air filter
0: Auto - Automatic
1: Manu - Manual
Manu
(1)
Auto
(0)
Manu
(1)
-
IS-S
PA25
Pressure switch air filter alarm delay
2
0
999
Sec
IS-S
PA26
Signal alarms pressure switch air filter
alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
PA28
Reset airflow meter alarm delay
30
0
999
Sec
IS-S
PA29
Airflow meter alarm delay
5
0
999
Sec
IS-S
PA30
Signal alarm air flow meter on alarm
relay
YES (1)
NO (0)
YES (1)
-
IS-S
PA31
Type of humidifier/hygrostat alarm
reset
0: Auto - Automatic
1: Manu - Manual
Auto
(0)
Auto
(0)
Manu
(1)
-
IS-S
PA32
Humidifier/hygrostat alarm delay
2
0
999
Sec
IS-S
PA33
Signal alarms humidifier/ hygrostat on
alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
PA34
Resistor circuit breaker alarm reset type
0: Auto - Automatic
1: Manu - Manual
Auto
(0)
Auto
(0)
Manu
(1)
-
IS-S
PA35
Heating element circuit breaker alarm
delay
2
0
999
Sec
IS-S
PA36
Anti-freeze alarm delay
5
0
999
Sec
IS-S
PA37
Signal alarm anti-freeze on alarm delay
YES (1)
NO (0)
YES (1)
-
IS-S
PA40
Enable RTC alarm
YES (1)
NO (0)
YES (1)
IS-S
PA41
Type of RTC alarm restoration
0: Auto - Automatic
1: Manu - Manual
Manu
(1)
Auto
(0)
Manu
(1)
-
IS-S
PA42
Signal RTC alarms on alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
PA45
Signal alarms fire/smoke on alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
MODBUS PARAMETERS
PH11
Board Modbus address
1
1
247
-
IS-M
PH12
Baud Rate of communication for the
card
(0=1200,
1=2400,
2=4800,
3=9600, 4=19200)
3
0
4
-
IS-M