EVCO EPK4BHQ1AH Installer manual User Manual
Page 34

EVCO S.p.A.
c-pro 3
NODE kilo AHU | Application manual ver. 1.0
page 34 of 114
PH13
ModBus
parity
(0=none,
1=Odd,
2=Even)
2
0
2
-
IS-M
PH14
Stop Bit ModBus (0=1bit, 1=2bit)
0
0
1
-
IS-M
VARIOUS PARAMETERS
PE01
Board’s IP address
192.16
8.0.2
0.0.0.0
255.25
5.255.2
55
-
IS-Et
PE02
SubNet mask for TCP/IP connection
255.25
5.255.0
0.0.0.0
255.25
5.255.2
55
-
IS-Et
PE03
Gateway for TCP/IP connection
192.16
8.0.1
0.0.0.0
255.25
5.255.2
55
-
IS-Et
VARIOUS PARAMETERS
PH01
Minimum value threshold for the
pressure sensor
0
0.0
PH02
Bar
IS-V
PH02
Maximum value threshold for the
pressure sensor
30.0
PH01
100.0
Bar
IS-V
PH03
Minimum temperature value for the Set
Point
-5.0
-15.0
PH04
°C
IS-V
PH04
Maximum temperature value for the Set
Point
40.0
PH03
70.0
°C
IS-V
PH05
Enable machine start-up/shut-down by
pressing the ESC/Stand-By key
YES (1)
NO (0)
YES (1)
-
IS-V
PH06
Enable the change in summer/winter
operating modes utilizing the keyboard
(ModE parameter)
YES (1)
NO (0)
YES (1)
-
IS-V
PH07
Enable the change in summer/winter
operating modes from DI
NO (0)
NO (0)
YES (1)
IS-V
PH08
Enable the change in summer/winter
operating modes: automatic change-
over
NO (0)
NO (0)
YES (1)
-
IS-V
PH09
Enable machine start-up/shut-down as
supervisor
NO (0)
NO (0)
YES (1)
IS-V
PH10
Enable the change in summer/winter
operating modes as supervisor
NO (0)
NO (0)
YES (1)
IS-V
PH18
Cancel alarm history
NO (0)
NO (0)
YES (1)
-
IS-V
Set
YES
(1)
and
wait
for
value NO
(0)
PH19
Enable machine start-up/shut-down by
schedule
NO (0)
NO (0)
YES (1)
IS-V
PH20
Enable scheduler
NO (0)
NO (0)
YES (1)
-
IS-V
PH21
Enable holiday function
NO (0)
NO (0)
YES (1)
-
IS-V