NODE kilo AHU | Application manual ver. 1.0

page 87 of 114

Note: each time the unit is in ON status (for turning on the card, for restoration of an alarm block, or to restore the

feed after a black-out), the dampers will re-align; for the entire run time (plus eventual time PS09), the shutter will

close and the control will be interrupted.

Once the run time has elapsed the control will return to its normal operating state. This is necessary because there is

no feedback for controlling the position of the shutter.

6.16.7

Damper status

In the user interface you can identify the operating status of the shutters which will present you with one of the

following:

1.

Disabled: the shutter is not managed by the controller. In the user interface you will see the symbol “ – “.

when in this state.

2.

Closed: the shutter is closed. In the user interface you will see written “CLOSED” and a value of 0.0%. when

in this status.

3.

Opening: the shutter is in the process of opening. In the user interface you will see written “OPENING

flashing with the corresponding value when in this state.

4.

Open: the shutter is open and still at the determined value. In the user interface you will see written “OPEN”

and the corresponding value of opening when in this state.

5.

Closing: the shutter is in the process of closing. In the user interface you will see written “CLOSING” flashing

with the corresponding value when in this state.

6.

Alignment: the shutter is in the process of moving in order to align in response to the start-up of the unit or

because the tension is restoring. In the user interface you will see written “ALIGNMENT.” with the value 0.0%

flashing.

6.17

Heat recovery devices

When the quantity of renewed air is substantive the air treatment centres provide a system which recovers the

exhaust air for a better exercise of energy costs.

Using the parameter (PG13>0) it is possible to utilize the heat recovery by selecting one of the following different heat

recovery devices:

-

PG13 = 0:

Management disabled

-

PG13 = 1:

Heat recovery devices at cross flow

-

PG13 = 2:

Heat recovery devices with double coil

-

PG13 = 3:

Heat recovery device rotating On/Off

-

PG13 = 4:

Heat recovery device rotating modulating

Recovery management presupposes that the exhaust air temperature sensor is present, therefore in order to utilize

the recovery the sensor will need to be enabled by setting parameter PH42=1.