4 modulating regulation – EVCO EPK4BHQ1AH Installer manual User Manual

Page 69

background image

EVCO S.p.A.

c-pro 3

NODE kilo AHU | Application manual ver. 1.0

page 69 of 114

SEtH:

Set

OFF

T. room

PF02:

ON

WINTER operating mode

6.10.4

Modulating regulation

Generally controlled by an inverter, it carries out a refined heating function: “winter operating mode” or cooling

function: “summer operating mode”. This control mode is focused on saving energy.

The variable fan speed is controlled by the room temperature sensor. The control set point (SEtC, SEtH) and the

proportional band (PF02) needs to be defined, see also the figures below. In order to enable this control select

PF01=3.

Alternatively the variable fan speed can be controlled by the discharge air temperature sensor (PF07).

Each mode of operation (summer/winter) has its own distinct control.

SUMMER operating mode WINTER operating mode

The fan speed is identical for both flow and return fans.

SEtH:

Set

PF03: Min.

T. room

PF02:

PF04:

Max.

Fan Speed

SEtC (SEtH): Set

PF03: Min.

T. room

PF02:

PF04:

Max.

Fan Speed