EVCO EPK4BHQ1AH Installer manual User Manual
Page 27

EVCO S.p.A.
c-pro 3
NODE kilo AHU | Application manual ver. 1.0
page 27 of 114
OE01
Economy Offset
0.0
-20.0
20.0
°C
UT
PSd1
Password for User Level (1)
0
-999
9999
-
UT
Level 2
MAINTENANCE OPERATOR MENU
CONTROL
PM00
Limit the maximum hours of fan
operation. Related alarms will sound if
maximum hours are exceeded.
20000
0
100000
Hrs
MA-F
PM01
Hours of fan operation - supply
0
0
100000
Hrs
MA-F
PM02
Hours of fan operation - return
0
0
100000
Hrs
MA-F
PM10
Limit the maximum hours of pump
operation. Related alarms will sound if
maximum hours are exceeded.
20000
0
100000
Hrs
MA-F
PM11
Hours of cooling pump operation
0
0
100000
Hrs
MA-F
PM12
Hours of heating pump operation
0
0
100000
Hrs
MA-F
PM90
Last date of machine maintenance
-
MA-F
MANUAL
PM22
Force the value of the fan in manual
operation (step)
0
0
3
MA-M
CALIBRATION
PM80
Calibration
of
the
outdoor
air
temperature sensor
0.0
-10.0
10.0
°C
MA-CA
PM81
Calibration of the room air temperature
sensor
0.0
-10.0
10.0
°C
MA-CA
PM82
Calibration
of
the
discharge
air
temperature sensor
0.0
-10.0
10.0
°C
MA-CA
PM83
Calibration of the room humidity sensor 0
-10
10
°C
MA-CA
PM84
Calibration
of
the
exhaust
air
temperature sensor
0.0
-10.0
10.0
°C
MA-CA
PM85
Calibration of the static pressure sensor 0.0
-10.0
10.0
Bar
MA-CA
PM86
Calibration of the air quality sensor
(CO2/VOC)
0
-100
100
ppm
MA-CA
PM87
Calibration of the discharge air humidity
sensor
0
-10
10
%
MA-CA
PM88
Calibration of the remote set-point
0.0
-10.0
10.0
°C
MA-CA
PM89
Calibration of the remote set-point
0.0
-10.00
10.00
°C
MA-CA
PSd2
Password Maintenance Operator Level
(2)
0
-999
9999
-
MA
Level 3
INSTALLATION OPERATOR MENU
CONTROL
PC01
Enable compensation Set Point summer
NO (0)
NO (0)
YES (1)
-
IS-R
PC02
Set
Point
maximum
for
summer
compensation
28.0
SEtC
PH04
°C
IS-R
PC03
Set Point (on external t.) at start
compensation
26.0
PH03
PH04
°C
IS-R
PC04
Differential
for
the
summer
compensation of Set Point
4.0
0.0
20.0
°C
IS-R