OE01

Economy Offset

0.0

-20.0

20.0

°C

UT

PSd1

Password for User Level (1)

0

-999

9999

-

UT

Level 2

MAINTENANCE OPERATOR MENU

CONTROL

PM00

Limit the maximum hours of fan

operation. Related alarms will sound if

maximum hours are exceeded.

20000

0

100000

Hrs

MA-F

PM01

Hours of fan operation - supply

0

0

100000

Hrs

MA-F

PM02

Hours of fan operation - return

0

0

100000

Hrs

MA-F

PM10

Limit the maximum hours of pump

operation. Related alarms will sound if

maximum hours are exceeded.

20000

0

100000

Hrs

MA-F

PM11

Hours of cooling pump operation

0

0

100000

Hrs

MA-F

PM12

Hours of heating pump operation

0

0

100000

Hrs

MA-F

PM90

Last date of machine maintenance

-

MA-F

MANUAL

PM22

Force the value of the fan in manual

operation (step)

0

0

3

MA-M

CALIBRATION

PM80

Calibration

of

the

outdoor

air

temperature sensor

0.0

-10.0

10.0

°C

MA-CA

PM81

Calibration of the room air temperature

sensor

0.0

-10.0

10.0

°C

MA-CA

PM82

Calibration

of

the

discharge

air

temperature sensor

0.0

-10.0

10.0

°C

MA-CA

PM83

Calibration of the room humidity sensor 0

-10

10

°C

MA-CA

PM84

Calibration

of

the

exhaust

air

temperature sensor

0.0

-10.0

10.0

°C

MA-CA

PM85

Calibration of the static pressure sensor 0.0

-10.0

10.0

Bar

MA-CA

PM86

Calibration of the air quality sensor

(CO2/VOC)

0

-100

100

ppm

MA-CA

PM87

Calibration of the discharge air humidity

sensor

0

-10

10

%

MA-CA

PM88

Calibration of the remote set-point

0.0

-10.0

10.0

°C

MA-CA

PM89

Calibration of the remote set-point

0.0

-10.00

10.00

°C

MA-CA

PSd2

Password Maintenance Operator Level

(2)

0

-999

9999

-

MA

Level 3

INSTALLATION OPERATOR MENU

CONTROL

PC01

Enable compensation Set Point summer

NO (0)

NO (0)

YES (1)

-

IS-R

PC02

Set

Point

maximum

for

summer

compensation

28.0

SEtC

PH04

°C

IS-R

PC03

Set Point (on external t.) at start

compensation

26.0

PH03

PH04

°C

IS-R

PC04

Differential

for

the

summer

compensation of Set Point

4.0

0.0

20.0

°C

IS-R