beautypg.com

Ultrasonic tab - peak combo – ADS Environmental Services ADS TRITON+ QR 775027 A3 User Manual

Page 203

background image

6-16 ADS TRITON+ Manual

Edit the Device Parameters located at the bottom of the dialog, and
then edit the individual tabs as described in the following sections.

Physical Offset Enter the measured physical offset for the
sensor at the time of installation if it was installed offset from
the bottom center of the pipe. Refer to Chapter 3, Sensor
Installation and Connection
, for instructions on measuring the
physical offset. The default physical offset is 0.

Channel Select the channel number of the port on top of the
monitor to which the device is physically connected.

Pipe Height This field displays the pipe height at the
monitoring point, based on the installation table. This
parameter is not editable from this location.

Note: Under normal conditions, the remaining parameters
corresponding to the Peak Combo device should not
require modification. However, if additional adjustments
are necessary, the following sections provide a detailed
description of each parameter.

Ultrasonic tab - Peak Combo

Edit the following parameters corresponding to the upward-looking
ultrasonic depth sensor in the Peak Combo Sensor:

Enable Select this checkbox to ensure the monitor begins
taking upward ultrasonic depth readings at the designated
interval upon activation. This option is selected by default.

Flow Type Select the option that best reflects the kind of
flow conditions that typically occur at the monitoring point
from the drop-down list:

Typical Flow exhibits a typical diurnal pattern. This is

the default setting.

Wet/Stagnant Flow remains in the pipe, but moves only

during wet weather events.

Usually Dry Pipe typically remains dry, except under

wet weather conditions.