Rockwell Automation 2090 Ultra3000 Servo Drives Integration Manual User Manual
Page 103
Publication 2098-IN005C-EN-P — March 2008
Troubleshooting Your Ultra3000 Servo Drive
103
E39
Self-sensing Commutation Startup Error
Motion required for self-sensing startup
commutation was obstructed.
•
Verify that there are no impediments to
motion at startup, such as hard limits.
•
Increase self-sensing current if high
friction or load conditions exist.
•
Check motor or encoder wiring using
wiring diagnostics.
E40
230V Shunt Protection Fault
Ineffective shunt resistor
•
Verify that the shunt resistor (internal or
external) is connected.
•
If an external shunt resistor is
connected, verify that the shunt fuse is
not blown.
•
If a non Allen-Bradley external shunt
resistor is used, verify that the
resistance value is within
specifications.
•
Verify that the motor is not being driven
mechanically, causing the motor to
behave as a generator.
Excessive regeneration
E41
460V Shunt Protection Fault
Ineffective shunt resistor
Excessive regeneration
E42
Motor Keying Error (SERCOS drives only)
The motor physically connected to the drive
differs from the motor specified in the user
program.
Select the correct motor in the user
program.
E43
Drive Enable Input
(SERCOS drives only)
•
An attempt was made to enable the
axis through software while the Drive
Enable hardware input was inactive.
•
The Drive Enable input transitioned
from active to inactive while the axis
was enabled.
•
Disable the Drive Enable Input fault.
•
Verify that Drive Enable hardware input
is active whenever the drive is enabled
through software.
E44
Lost motion fault
(only applies to applications with
Stegmann feedback devices)
Detection occurs during a fault reset.
Absolute position in the drive is incorrect
and the motion has been lost due to line
loss condition.
•
Cycle power.
•
Cycle power and re-home drive if drive
was homed in the same power cycle
that the lost motion fault occurred.
E50
Duplicate Node Fault
(SERCOS drives only)
Duplicate node address detected on
SERCOS ring.
Verify that each SERCOS drive is assigned
a unique node address.
All others
RESERVED
Call your local Allen-Bradley
representative.
Error
Code
Problem or Symptom
Possible Cause
Action/Solution