Chapter 3

Component Definition and Maintenance

Replacing Transient Suppression Network Fuses

Two sizes of fuses (5 kV, 7.2 kV) are available within the TSN located inside the
connection cabinet. The 18 Pulse drive contains three TSNs.

1.

Ensure there is no power to the equipment.

2.

Fuses are held in a place with a fuse clip. To remove the fuse pull firmly.

3.

To replace the fuse, hold it in position and push firmly until the fuse is
seated within the fuse clip. Install fuses so that the rating is visible.

Figure 28 - Transient Suppression Network

ATTENTION: To prevent electrical shock, disconnect the main power before
working on the drive. Verify that all circuits are voltage-free using a hot stick or
appropriate voltage-measuring device. Failure to do so may result in injury or
death.

IMPORTANT

Replace the fuse with another of the same rating. (See

Figure 28 on page 38

for

location.)

Ground location

Varistors

5 kV fuse example

7.2 kV fuse example

Connecting links

Varistors

5 kV fuse location

7.2 kV fuse location