Component Definition and Maintenance

Chapter 3

Figure 112 - AFE/18 Pulse Remote Transformer / Starter

AC/DC Power Supply

The load demands on the AC/DC converters are the DC/DC converter and up
to six IGDPS modules (up to three IGDPS modules for SPS drives). The
DC/DC is a fixed load; however, the quantity of IGDPS modules will vary
depending upon the drive configuration and whether SPS modules are used.

The AC/DC power supply accepts single phase voltage and produces a regulated
56V DC output for the DC/DC power supply and the HV IGDPS modules that
power the SGCTs. The input and output voltages are monitored and fail signals
are annunciated upon either voltage going below a pre-set level.

Figure 113 - AC/DC Converter Power Supply

DC FAIL: Upon loss of DC output (V outputs ≤ 49V DC) this output goes
from low to high. The AC/DC power supply is located in the low voltage panel
at the top right-hand section of the drive. A typical low voltage compartment is
shown in

Figure 114

.

18 Pulse

AFE

DC/DC Converter

AC/DC Converter

56V DC

600 W/ 1000W/

1500 W

Line

Filter

Customer

Supplier

120V 1-ph

- Printer

- Operator Interface

- Relays

C Hold-up

Sense Cable

20V Isolated

Gate Driver

Power Supply

Inverter only for SPS Drives

20V

24V-Isolators
24V-XIO

+/-24V-HECS

+/-15V Logic

5V-Logic

VFD

Fan

380V 50 Hx

or

460V 60 Hz

3-ph

Tx Fan

VFD

Fan

Tx Fan

380V 50 Hx

or

460V 60 Hz

3-ph

AC/DC Power Supply

56V DC

600 W/ 1000 W/

1500 W

HV IGDPS

Power

Supply

DC/DC Power

Supply

DC Fail

Single Phase
95...265V AC

47...63 Hz

0.98PF@1000 W or

0.98PF@1500 W