Rockwell Automation Publication 7000-UM202B-EN-P - June 2014

15

PowerFlex 7000 Overview

Chapter 2

Figure 2 - 3300/4160V Direct-to-Drive (transformerless AFE rectifier)

AFE Rectifier with Separate Isolation Transformer

For applications when the line voltage is higher than the motor voltage, a
transformer is required for voltage matching. In this case, providing an AFE
rectifier with a separate isolation transformer is ideal (indoor and outdoor
transformer versions are offered). The isolation transformer provides the input
impedance (replaces the requirement for an integral line reactor) and addresses
the common mode voltage (replaces the requirement for a CMC that is supplied
in the Direct-to-Drive rectifier configuration). However, the AFE rectifier, its
operation, and advantages are the same as the Direct-to-Drive configuration.

Figure 3 - 3300/4160 AFE Rectifier with separate isolation transformer