beautypg.com

Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control User Manual

Page 144

background image

144

Rockwell Automation Publication 7000-UM202B-EN-P - June 2014

Chapter 3

Component Definition and Maintenance

7.

Remove the Drive Processor Module from the four, 34-pin female
connectors and one, 16-pin female connector on the ACB.

8.

Remove the DIM module from the DPM and plug it on the new DPM
before replacing the DPM.

9.

Reverse steps 7 – 3 to re-install the boards into the low voltage control
cabinet.

10.

Apply control power to the drive. The DPMs ship without installed
firmware, so the drive will shift into download mode. Install firmware in
the drive following the guidelines the Installation Manual.

11.

Program the drive. See publication

7000-TD002_-EN-P

. Save the

parameters to NVRAM and externally, using the options described earlier
in this section.

Figure 130 - ACB and DPM Replacement

ANALOG

CONTROL

BOARD

Analog Control Board
(ACB)