The fuses are E-rated, current-limiting fuses with a high interrupting rating.
Because they are current-limiting, they limit both the magnitude and duration of
fault currents. They are small dimension, ferrule-type fuses with a fiberglass body,
and mount in standard fuse clips.

Figure 27 - Simplified wiring diagram

IMPORTANT

Rockwell Automation selects the fuses sent with the Transient Suppression
Network based on their characteristics (including internal resistance) for
optimum MOV performance and protection. Do not substitute other fuses
without contacting the factory first.

IMPORTANT

Voltage sensing occurs after the MOV fuse and will detect open fuses in the
drive control as a Master or Slave Undervoltage or Unbalance.

U

V

W

Drive Input Power from Line Terminals

Transient Suppression Network
Medium Voltage Input Fuses

Phase MOV Suppressor

Ground MOV Suppressor