Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control User Manual
Page 202
202
Rockwell Automation Publication 7000-UM202B-EN-P - June 2014
Appendix G
Encoder Use and Torque Capabilities
•
When cable lengths exceed 305 m (1000 ft) for the Northstar or 610 m
(2000 ft) for the Avtron, consult the factory.
Table 14 - Encoder Selection
PowerFlex 7000 Drive
Performance (Torque
Capabilities)
The PowerFlex 7000 drives have been tested on a dynamometer to verify
performance under locked rotor, accelerating, and low speed-high torque
conditions.
shows the PowerFlex 7000 drive torque capabilities as a
percent of motor rated torque, independent of the drive’s momentary overload
conditions.
Table 15 - PowerFlex 7000 Drive Torque Capabilities
High Performance
Torque Control (HPTC)
Mode
Motor RPM
Minimum Tach PPR
Recommended Tach PPR
3600
1024
1024
3000
1024
1024
1800
1024
2048
1500
1024
2048
1200
2048
2048
1000
2048
2048
900
2048
4096
720
4096
4096
600
4096
4096
450
4096
8192
360
8192
8192
300
8192
8192
Standard Control Mode
3600
—
600
3000
—
600
1800
—
1024
1500
—
1024
1200
—
2048
1000
—
2048
900
—
2048
720
—
2048
600
—
2048
Parameter
7000 Torque Capability
without Encoder (% of
Motor Rated Torque)
7000 Torque Capability
with Encoder (% of
Motor Rated Torque)
7000 Torque Capability with
Encoder and High Performance
Torque Control (HPTC)
Breakaway Torque
90%
150%
150%
Accelerating Torque
90% (0...8 Hz)
140% (0...8 Hz)
150% (0...75 Hz)
125% (9...75 Hz)
140% (9...75 Hz)
Steady State Torque
125% (9...75 Hz)
(1)
100% (1...2 Hz)
150% (0...60 Hz)
(1)
140% (3...60 Hz)
(1)
(1) Drive will require over-sizing to achieve greater than 100% continuous torque.
Max. Torque Limit
150%
150%
150%