Component Definition and Maintenance

Chapter 3

Figure 118 - Terminal locations on 600W AC/DC Power Supply (Cosel)

Output Calibration

Ensure the output of the supply is 56V DC.

There is a potentiometer on the top of the power supply that adjusts the 56 Volt
DC output for the power supply. Isolate the output of the power supplies;
multiple supplies in series will affect your measurements. With the control power
on and the output of the AC/DC Converter isolated from the drive control,
adjust the potentiometer until the output equals 56 volts DC. Perform this test
on each power supply. When all adjustments are complete, reconnect the power
supply to the circuit and re-measure the output. Readjust if necessary.

If it is not possible to maintain 56 V DC, the power supply may be faulty.

Terminal/Connections
Descriptions
(600W Cosel Power Supply)

Single Phase Input

DC Outputs

Control Signals

Air Flow

FRONT VIEW

P1-AC Input

PIN#

LABEL

AC (L)

Live

AC (N)

Neutral

NC

No Connection

FG

Earth

P2-DC Output

PIN#

LABEL

+

+56V

+56V COMM

P3-Fail Output

PIN#

LABEL

CN1

1-2 Connected
3-4 Connected
5, 6, 7, 8, 9, 10 N/C

CN2

N/C

CN3

7 - Alarm
8 - Alarm GND