beautypg.com

Power supply replacement – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control User Manual

Page 132

background image

132

Rockwell Automation Publication 7000-UM202B-EN-P - June 2014

Chapter 3

Component Definition and Maintenance

Power Supply Replacement

1.

Ensure control power has been isolated and locked out.

2.

Disconnect the terminals at the unit.

3.

Remove the four M6 bolts (

Figure 122

).

4.

Extract the power supply complete with bracket from the drive.

5.

Remove the bracket(s) from the failed power supply (four M4 screws and
nylon shoulder washers).

6.

Attach bracket to replacement power supply. Ensure the Black
Insulation(s) is between the AC/DC power supply and the mounting
plate(s).

7.

Repeat Steps 5, 4, 3, 2 and 1 in this order to replace the unit.

8.

Reapply control power and verify voltage levels.

Figure 119 - Replacing AC/DC power supply (1000/1500W Pioneer) on LV panel (heat sink model)

Black insulation

Bracket

M6 bolts

M6 bolts