beautypg.com

Rockwell Automation 25-COMM-E2P PowerFlex 25-COMM-E2P Dual-Port EtherNet/IP Adapter User Manual

Page 30

background image

30

Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013

Chapter 3

Configuring the Adapter

7.

In the BOOTP/DHCP Request History list, either double-click the
adapter’s Ethernet Address (MAC) noted in Step 2, or click New in the
Relation List. The New Entry window appears. In the first case, the
Ethernet Address (MAC) is automatically entered. In the latter case, you
must manually enter it.

8.

Edit the following:

9.

Click OK to apply the settings. The adapter appears in the Relation List
with the new settings.

10.

To assign this configuration to the adapter, select the device in the Relation
List and click Disable BOOTP/DHCP. When power is cycled on the
drive, the adapter will use the configuration you assigned it and not issue
new BOOTP/DHCP requests.

11.

To save the Relation List, select File > Save.

Box

Type

IP Address

(1)

(1) For definitions of these terms, see the

Glossary on page 161

.

A unique IP address for the adapter

Host Name

Optional

Description

Optional

TIP

To enable BOOTP for an embedded adapter that has had BOOTP
disabled, first select the adapter in the Relation List. Then, depending
on the type of server, click Enable BOOTP or Enable DHCP and,
lastly, reset the adapter or power cycle the drive.