Commissioning the adapter – Rockwell Automation 25-COMM-E2P PowerFlex 25-COMM-E2P Dual-Port EtherNet/IP Adapter User Manual
Page 24
24
Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Chapter 2
Installing the Adapter
2.
Set the value of
Host parameter P047 [Speed Reference1]
to 4 “Network Opt”.
For more information on how to set different combinations of the control and
Reference functions, see the PowerFlex 525 drive user manual,
publicatio
.
Commissioning the Adapter
To commission the adapter, you must set a unique network node address. See the
for details about IP addresses. When using the Node
Address switches, see
Setting the Node Address on page 15
for details. When not
using these switches, a BOOTP or DHCP server, or adapter parameters can be
used to set the node address after connecting the adapter to the network and
applying power to the drive.
By default, the adapter is configured so that you must set the node address using a
DHCP server. For details, see
Using a BOOTP or DHCP Server on page 28
. To
set the node address using adapter parameters, see
TIP
The PowerFlex 525 drive supports up to three control functions and
three Reference functions.
IMPORTANT
New settings for some adapter parameters (for example, Device parameters 06
[IP Addr Cfg 1] through 09 [IP Addr Cfg 4]) are recognized only when power
is applied to the adapter or it is reset. After you change parameter settings,
cycle drive power or reset the adapter.