8

Commissioning of the CANopen Logic bus

8.11

Preparing the restart

61

Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.11.3

Special features of the I/O system 1000 (EPM-Sxxx)

There are different possibilities for restarting the I/O system:

• Automatically
• Automatically with factory adjustment
• Using the »Engineer«

For the corresponding settings, first tick the "Expert settings" on the CANopen Remote Device tab.

8.11.3.1

Automatic restart

Settings for automatic initialisation by the Lenze Controller:

1. Enter all desired parameter values under the All parameters tab.

2. Tick "Create all SDOs" under the CANopen Remote Device tab.

When the I/O system has been replaced

1. Set the node address and the baud rate at the code switch.
2. Start the Lenze Controller..