beautypg.com

11 preparing the restart, Preparing the restart ( 59), 8commissioning of the canopen logic bus – Lenze CANopen Controller-based Automation User Manual

Page 59

background image

8

Commissioning of the CANopen Logic bus

8.11

Preparing the restart

59

Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.11

Preparing the restart

In the control technology system you can use the Lenze Controller to transmit the complete

parameter setting via SDO initialisation to the field devices when the machine is switched on.
According to DS301, the Lenze Controller always initialises the CAN parameters of the field devices.

Additionally the controller can initialise further parameters. The values for this must be stored in

the Control configuration under the Service Data Objects tab.
Usually, the Lenze Controller only transmits the SDO objects for which you have stored another

value than the standard value. The controller does not compare these values with the existing

values in the field device. Thus, not all parameters changed there may be set correctly.
If you want a factory adjustment to be carried out in the field device before the SDO initialisation is

carried out, tick under the CANopen Remote Device tab ...

1. "Enable Expert Settings",
2. "Default Settings":

The Service Data Objects tab contains the codes which are written in the EDS file. The EDS file

contains all writable codes.

Note!

During a factory adjustment, the parameter setting in the field device, which you have

carried out with the »Engineer«, gets lost. In this case, you have to transmit all parameter

values manually to the Service Data Objects tab. This only makes sense when

commissioning is completed and all parameters are optimised. If you change something

afterwards via the »Engineer«, you have to maintain it in the PLC program.