Technical data

5.4

Bus cable length

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Example: Check use of repeater

Conclusion:

• It is not possible to use a cable length of 450 m without using a repeater.
• After 360 m (test step 2) a repeater has to be used.

Result:

• The Lenze repeater, type 2176 (cable reduction: 30 m), is used
• Calculation of the maximum cable length:

• First segment: 360 m
• Second segment: 360 m (see table

Segment cable length

( 22)

) minus 30 m (cable reduction

for a repeater)

• Max. achievable cable length with a repeater: 690 m

• The selected cable length can be implemented.

Given:
Baud rate

125 kbps

Cable cross-section

0.5 mm

2

Number of nodes

28

Cable length

450 m

Test step

Cable length

See table ...

1 Total cable length at 125 kbps:

630 m

Total cable length ( 22)

2 Segment cable length for 28 nodes and a cable cross-

section of 0.5 mm

2

:

360 m

Segment cable length ( 22)

3 Comparison: The detected segment cable length is

smaller than the total cable length of 450 m to be

achieved.