5 technical data, 1 general data, Technical data – Lenze CANopen Controller-based Automation User Manual
Page 20: General data, 5technical data
![background image](/manuals/565683/20/background.png)
Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17
20
5
Technical data
5.1
General data
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5
Technical data
5.1
General data
Area
Values
Communication profile
CANopen (DS301, V4.02)
Standards
CAN, ISO 11898 / EN 50325-4
Network topology
Line, terminated at both ends with 120
(e.g. terminated with Sub-D plug of type EWZ0046)
Max. number of nodes
127
Adjustable node addresses
1 ... 127
(adjustable for Lenze devices via DIP switches)
Baud rates [kbps]
• 10
• 20
• 50
• 125
• 250
• 500
• 1000
Parameter data
Max. 10 client and server SDO channels with 1 ... 8 bytes
Cycle time - Motion/CNC task
1 ... 16 ms
Number of drives/ms on the Motion
bus
Max. 3 drives/ms
Signal propagation delay drive
controller
drive
4 cycles
Cross communication
Only possible with CANopen (Logic)
In the case of CANopen (Motion), communication is executed centrally via
the Lenze Controller.
Number of DI + DO (bits/ms)
384 (max. 6 PDOs/ms on the Logic bus)
Cycle synchronisation with locked
PLL (Jitter)
+/-10 μs