Commissioning of the CANopen Logic bus

8.9

Setting of CAN parameters and PDO mapping

53

Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.9.1

Cross communication between the slaves

With control via the CAN bus, cross communication between the slaves is possible. For this purpose,

you must configure the CAN communication and the PDO mapping in the »Engineer« and write it

to the controllers.
Since the mapping for the cross communication between the slaves is not available in the control

configuration, you must set the "No initialisation" option in the »PLC Designer« on the CANopen

Remote Device tab of the respective slaves.

Thus the CAN settings and mapping settings in the slave drives will not be overwritten by the Lenze

Controller when the PLC program starts.

Note!

In addition to the cross communication between the slaves, communication with the

master must also be configured in the »Engineer«.
If the "No initialisation" option is active, this part of the PDO mapping is also not

overwritten by the Lenze Controller.