Notes regarding the visualisation using »VisiWinNET«

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

14.6

Notes regarding the visualisation using »VisiWinNET«

Problem description:
For visualisation purposes a "VWGET" timer (1 second) is used to read a variable via the CAN bus

(SDO) using the OPC server. If no nodes are connected and no information is returned, a time-out is

generated. Waiting for the time-out causes the page-turning function of the visualisation program

to slow down.

Solution:
The visualisation program can be operated again if the following lines of the time-out are changed

in the PostStart.txt file:

Otherwise "VWSET" and "VWGET" must not be used for visualisation purposes.

[HKEY_LOCAL_MACHINE\Drivers\BuiltIn\CAN2Bus1]
"SDOTimeout"=dword:0xc8
"Timeout"=dword:0xc8