beautypg.com

3 use of repeaters, Use of repeaters, 5technical data – Lenze CANopen Controller-based Automation User Manual

Page 23

background image

5

Technical data

5.4

Bus cable length

23

Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.4.3

Use of repeaters

Compare the values from the tables

Total cable length

( 22)

and

Segment cable length

( 22)

.

If the detected segment cable length is smaller than the total cable length to be achieved, repeaters

must be used.

Example: Detecting cable lengths / number of repeaters

At the maximum number of nodes (127), the following cable lengths/number of repeaters from the

specifications have to be observed:

Given:
Cable cross-section

0.5 mm

2

, according to

Bus cable specification ( 21)

Number of nodes

127

Repeater

Lenze repeater, type 2176 (cable reduction: 30 m)

Baud rate [kbps]

10

20

50

125

250

500

800

1000

Max. cable length [m]

8000

3900

1500

630

290

110

40

17

Segment cable length [m]

270

270

270

270

270

110

40

17

Number of repeaters

33

16

6

2

1

-

-

-