Bus cable length
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4
Bus cable length
5.4.1
Total cable length
The total cable length is also specified by the baud rate.
5.4.2
Segment cable length
Repeaters divide the total cable length into segments. The segment cable length is defined by the
cable cross-section and the number of nodes per segment. Without a repeater, the segment cable
length corresponds to the total cable length.
Note!
• It is absolutely necessary to comply with the permissible cable lengths.
• Observe the reduction of the total cable length due to the signal delay of the repeater.
• If the total cable lengths of the nodes are different at the same baud rate, the smaller
value must be used to determine the max. cable length.
Baud rate [kbps]
Max. bus length [m]
Servo Drives
9400
Inverter Drives
8400
I/O-System 1000
(EPM-Sxxx)
CANopen bus coupler
10
8000
-
5000
20
4000
-
2500
50
1500
1500
1000
125
600
600
500
250
275
275
250
500
110
110
80
1000
13
13
25
Max. number of
nodes per segment
Cable cross-section
0.25 mm
2
0.50 mm
2
0.75 mm
2
1.00 mm
2
2
240 m
430 m
650 m
940 m
5
230 m
420 m
640 m
920 m
10
230 m
410 m
620 m
900 m
20
210 m
390 m
580 m
850 m
32
200 m
360 m
550 m
800 m
63
170 m
310 m
470 m
690 m
100
150 m
270 m
410 m
600 m