Commissioning of the CANopen Logic bus

8.10

Creating the program code for controlling the Logic field device

57

Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.10

Creating the program code for controlling the Logic field device

If the device descriptions for logic devices that are supplied with the »PLC Designer« are

used, the process data are copied to the subordinate logic drive node automatically. (For

further information see SW_Commissioning_Lenze_(Controller-based)_Vx-y_EN.pdf,

chapter "Overview of device descriptions".)

If the process data are to be continued to be linked manually, go to the LenzeLogicDrive

Configuration tab and activate this option:

Then continue to create the program code.

Note!

All program blocks which are operated with an SDO communication must be called up

in the same Logic task. Otherwise, jobs will get lost.