Technical data, Assignment of external mains chokes – Lenze 8400 User Manual
Page 58
Technical data
Rated data
Operation with increased power at a 400 V mains
4
58
EDS84ASC552 EN 9.1
Mains current at I
aN
Apparent output power
Motor power
with external
mains choke
without external
mains choke
U, V, W
4 pol. ASM
Type
I
LR
[A]
I
LR
[A]
S
aR
[kVA]
P
aR
[kW]
E84AVxxx3714
1.7
2.2
1.0
0.55
E84AVxxx5514
2.6
3.2
1.4
0.75
E84AVxxx7514
3.0
-
1.8
1.1
E84AVxxx1124
3.8
5.3
2.4
1.5
E84AVxxx1524
4.7
6.6
3.0
2.2
E84AVxxx2224
6.1
-
4.2
3.0
E84AVxxx3024xxS
8.4
-
5.5
4.0
E84AVxxx3024xx0
8.4
11.8
5.5
4.0
E84AVxxx4024
10.6
15.7
7.2
5.5
E84AVxxx5524
18.0
-
9.7
7.5
E84AVxxx7524
21.0
28
13.1
11
E84AVxxx1134
29.0
-
17.6
15
E84AVxxx1534
1)
-
-
-
-
E84AVxxx1834
42.2
-
29.2
22
E84AVxxx2234
1)
50.8
-
35.2
30
E84AVxxx3034
1)
66.0
-
45.6
37
E84AVxxx3734
1)
81.6
-
56.9
45
E84AVxxx4534
1)
96.0
-
66.6
55
1)
only with external mains choke
Assignment of external mains chokes
Assignment
Type
Mains choke required
Mains choke
E84AVxxx3714
no
ELN3-1500H003-001
E84AVxxx5514
no
E84AVxxx7514
yes
ELN3-0680H006-001
E84AVxxx1124
no
E84AVxxx1524
no
E84AVxxx2224
yes
ELN3-0500H007-001
E84AVxxx3024xxS
yes
ELN3-0250H013-001
E84AVxxx3024xx0
no
ELN3-0250H013-001
E84AVxxx4024
no
ELN3-0250H013-001
E84AVxxx5524
yes
ELN3-0170H017-001
E84AVxxx7524
no
ELN3-0150H024-001
E84AVxxx1134
yes
ELN3-0088H035-001
E84AVxxx1534
-
-
E84AVxxx1834
yes
ELN3-0075H045-001
E84AVxxx2234
yes
ELN3-0055H055-001
E84AVxxx3034
yes
ELN3-0038H085-001
E84AVxxx3734
yes
E84AVxxx4534
yes
ELN3-0027H105-001