Technical data, Rated data operation at rated mains voltage 230 v – Lenze 8400 User Manual
Page 38
Technical data
Rated data
Operation at rated mains voltage 230 V
4
38
EDS84ASC552 EN 9.1
Fuses and cable cross-sections
Operation without external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
L1, N - laying system
L1, N
B2
C
F
[A]
[A]
[mm
2
]
[mm
2
]
[mm
2
]
[A]
[AWG]
[mA]
E84AVxxx2512
C 6
6
1
-
-
6
18
30
3)
E84AVxxx3712
C 6
6
1
-
-
10
16
E84AVxxx5512
C 10
10
1.5
-
-
10
16
30
3)
E84AVxxx7512
C 10
10
1.5
-
-
15
14
E84AVxxx1122
C16
16
2.5
-
-
20
12
30
3)
E84AVxxx1522
C 20
20
4.0
-
-
25
10
E84AVxxx2222
C 25
25
6.0
-
-
30
10
1)
These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298-4).
The cable-cross sections apply under the following conditions: Use of PVC-insulated copper cables, conductor
temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, two loaded cores. Smaller cable
cross-sections are not permissible for technical reasons.
2)
Use UL-approved cable, fuses, and fuse holders only.
UL fuse: voltage 240 V, tripping characteristic for example ”H”, ”K5” or ”CC”.
The cable cross-sections apply under the following conditions: conductor temperature < 75 °C, ambient temperature
< 45°C. Smaller cable cross-sections are not permissible for technical reasons.
3)
Pulse-current sensitive or universal-current sensitive earth-leakage circuit breaker, short-time delay
If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and
switching frequency.
Circuit breaker
Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category
Fuse
Observe national and regional regulations