Technical data, Rated data operation at rated mains voltage 400 v – Lenze 8400 User Manual
Page 46
Technical data
Rated data
Operation at rated mains voltage 400 V
4
46
EDS84ASC552 EN 9.1
Operation with external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
L1, L2, L3 - Laying system
L1, L2, L3
B2
C
F
[A]
[A]
[mm
2
]
[mm
2
]
[mm
2
]
[A]
[AWG]
[mA]
E84AVxxx3714
C 6
6
1.0
-
-
6
18
30
3)
E84AVxxx5514
C 6
6
1.0
-
-
6
18
E84AVxxx7514
C 6
6
1.0
-
-
6
18
E84AVxxx1124
C 6
6
1.0
-
-
10
16
30
3)
E84AVxxx1524
C 6
6
1.0
-
-
10
16
E84AVxxx2224
C 10
10
1.5
-
-
10
16
E84AVxxx3024xxS C 10
10
1.5
-
-
15
14
300
3)
E84AVxxx3024xx0 C 10
10
1.5
-
-
15
14
300
3)
E84AVxxx4024
C 16
16
2.5
-
-
20
12
E84AVxxx5524
C 20
20
4
-
-
20
12
E84AVxxx7524
C 20
20
4
2.5
-
20
12
300
3)
E84AVxxx1134
C 32
32
10
10
-
30
10
E84AVxxx1534
C 32
32
10
10
-
40
8
E84AVxxx1834
C 50
50
16
10
-
40
8
300
3)
E84AVxxx2234
C 63
63
25
16
-
50
6
E84AVxxx3034
C 80
80
-
16
-
70
4
300
3)
E84AVxxx3734
C100
100
-
25
-
80
4
E84AVxxx4534
C125
125
-
50
-
100
3
1)
These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298-4). The cable cross-sections apply under the following conditions: Use of PVC-insulated copper cables,
conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: voltage 500 V, tripping characteristic for example ”H”, ”K5” or ”CC”. The cable cross-sections apply under
the following conditions: conductor temperature < 75 °C, ambient temperature < 45°C.
3)
Universal-current sensitive earth-leakage circuit breaker, short-time delay
If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and
switching frequency.
Circuit breaker
Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category
Fuse
Observe national and regional regulations