Electrical installation

TopLine C control terminals

Axis bus

6

240

EDS84ASC552 EN 9.1

Data transfer axis bus

Labelling

Feature

Rated value

X10/AH, AL

Data transfer axis bus connection

Acc. to CAN specification

Cable lengths: See CAN on board

Baud rate

from version 12.00: 800 kbit/s, constant

up to version 2.xx: 500 kbps, constant

Terminating resistor

120 , switching via DIP switch

X10/AG

GND, reference potential: Data transfer axis bus

Note!

Trouble-free operation of the axis bus is only possible if the following

requirements are met:

ƒ

Use CAN cables in accordance with ISO 11898

ƒ

Apply cable shields to both ends of the shield connections (functional earth)

In particular for longer cables, in the case of installation over several control

cabinets, or in difficult EMC environments, further measures are required:

ƒ

Establish equipotential bonding between the places of installation ( 167)

ƒ

Use of a power choke at the mains connection