beautypg.com

Electrical installation, Stop – Lenze 8400 User Manual

Page 179

background image

Electrical installation

Devices in the power range 0.25 ... 2.2 kW (1/N/PE AC 230 V)

Example circuits

6

179

EDS84ASC552 EN 9.1

Operation with rated power at the 230V mains, 3/PE

Stop!

Destruction of the device
Devices with a 230V mains connection must not be connected to a

three-phase 400V mains.
Possible consequences:

ƒ

The device will be destroyed

Protective measures:

ƒ

Check the voltage between the phase conductors L1 and L2. It must not

exceed 230/240V.

The devices in the power range of 0.25kW to 2.2kW can also be connected to a three-phase

230V mains. In this case, the following conditions must be observed:

ƒ

Both mains phases L1 and L2 must be fused.

ƒ

If the drive controller is connected to the mains via a contactor or similar, both

mains phases L1 and L2 must be switched via the contactor.

3/PE AC 230 V

L1

N

L1

L2
L3

PE

F1

F2

PE

X100

+

8400GG085

Fig. 6-11

Supplied by a three-phase 230V mains

Note!

The discharge current against ground is higher than when supplied via a

one-phase 230V mains. If necessary, the application of a safety switch with a

higher fault current must be observed.

This manual is related to the following products: