Technical data, General data and operating conditions – Lenze 8400 User Manual
Page 30

Technical data
General data and operating conditions
4
30
EDS84ASC552 EN 9.1
Motor cable length (shielded)
after interference suppression and required earth-leakage circuit breaker
U
rated
P
rated
With LL filter
With SD filter
With LD filter
[V]
[kW]
30 mA FI
30 mA FI
300 mA FI
230
0.25 ... 2.2
5 m
25 m
50 m
400/500
0.37 ... 2.2
-
25 m
1)
50 m
1)
400/500
3.0 ... 15
-
25 m
50 m
400/500
18.5 ... 45
-
-
50 m
1)
Observe switching frequency-dependent restrictions according to table ”Motor cable lengths without considering EMC
limit values”
Device-dependent filter assignments: See chapter ”Accessories”, 11.3 and 11.4
If LL filters are used, the fault current is 3.5 mA. Fixed installation is not required.