Mechanical installation
Standard devices in a power range of 0.25 ... 3 kW
Mounting in ”cold plate” technique
5
103
EDS84ASC552 EN 9.1
5.2.3
Mounting in ”cold plate” technique
The E84AVxxC... controllers are designed for assembly on coolers (e.g. collective coolers) in
”cold-plate” technique.
Requirements for collective coolers
A good thermal connection to the cooler is important for the trouble-free operation of
the controller:
ƒ
The contact area between the collective cooler and the controller
– must be at least as big as the cooling plate of the controller.
– must be smooth, the maximum deviation must not exceed 0.05 mm.
ƒ
The collective cooler must be connected to the controller with all required screwed
joints.
ƒ
The thermal resistance R
th
must be observed, see table.
The values in the table apply to the operation of the controllers under rated
conditions.
The values include the heat transmission between the cooler and the device.
With a standard heat conducting paste and a film thickness of 50 m, the heat
transmission is approx.
– 0.03 K/W for controllers up to 5.5 kW
– 0.02 K/W for controllers up to 15 kW
– 0.01 K/W for controllers up to 22 kW.
Power to be dissipated
Thermal resistance
Type
P
v [W]
R
th
[K/W]
E84AVxxC2512
15
1.5
E84AVxxC3712
20
1.5
E84AVxxC5512
30
1.0
E84AVxxC7512
40
1.0
E84AVxxC1122
60
0.6
E84AVxxC1522
75
0.5
E84AVxxC2222
100
0.4
E84AVxxC3714
25
1.0
E84AVxxC5514
35
1.0
E84AVxxC7514
50
1.0
E84AVxxC1124
60
0.6
E84AVxxC1524
70
0.5
E84AVxxC2224
100
0.4
E84AVxxC3024xxS
100
0.4