3 operation at rated mains voltage 400 v, Operation at rated mains voltage 400 v, Technical data – Lenze 8400 User Manual
Page 40: Rated data operation at rated mains voltage 400 v

Technical data
Rated data
Operation at rated mains voltage 400 V
4
40
EDS84ASC552 EN 9.1
4.2.3
Operation at rated mains voltage 400 V
Basis of the data
Mains
Voltage
Voltage range
Frequency range
U
Lrated
[V]
U
Lrated
[V]
f [Hz]
3/PE AC
400
320 - 0 % ... 440 + 0 %
45 - 0 % ... 65 + 0 %
Mains current at I
aN
Apparent output power
Motor power
with external
mains choke
without external
mains choke
U, V, W
4 pol. ASM
Type
I
LR
[A]
I
LR
[A]
S
aR
[kVA]
P
aR
[kW]
E84AVxxx3714
1.4
1.8
0.8
0.37
E84AVxxx5514
2.2
2.7
1.1
0.55
E84AVxxx7514
2.5
3.6
1.5
0.75
E84AVxxx1124
3.2
4.4
2.0
1.1
E84AVxxx1524
3.9
5.5
2.4
1.5
E84AVxxx2224
5.1
7.3
3.5
2.2
E84AVxxx3024xxS
7.0
9.8
4.6
3.0
E84AVxxx3024xx0
7.0
9.8
4.6
3.0
E84AVxxx4024
8.8
13.1
5.9
4.0
E84AVxxx5524
12.0
18
8.1
5.5
E84AVxxx7524
15.0
20.0
10.3
7.5
E84AVxxx1134
21.0
29.0
14.7
11.0
E84AVxxx1534
1)
29.0
-
20.0
15.0
E84AVxxx1834
36.0
50.4
24.9
18.5
E84AVxxx2234
1)
42.0
-
29.3
22.0
E84AVxxx3034
1)
55.0
-
38.0
30.0
E84AVxxx3734
1)
68.0
-
47.4
37.0
E84AVxxx4534
1)
80.0
-
55.5
45.0
1)
only with external mains choke