Technical data, General data and operating conditions – Lenze 8400 User Manual
Page 28
Technical data
General data and operating conditions
4
28
EDS84ASC552 EN 9.1
Supply conditions
AC mains operation
Direct connection
Power systems
TT
Operation permitted without restrictions
TN
With earthed phase
EN 61800-5-1
Operation permitted if additional measures are taken:
Overvoltage reduction to overvoltage category II required.
If protection against accidental contact is required for the
control terminals, external measures must be taken.
The measures described for IT systems must be taken.
Operation is not permissible:
With integrated safety system, e.g. E84AVxxxxxxxxBx
IT
Observe instructions regarding special measures.
DC-bus operation
Direct connection possible for devices with 400 V mains
connection.
Motors
Only use motors suitable for inverter operation. Lenze L-force
motors comply with the requirements.
Environmental conditions
Climate
Storage
IEC/EN 60721-3-1
1K3 (-25 ... +60 °C)
Transport
IEC/EN 60721-3-2
2K3 (-25 ... +70 °C)
Operation
IEC/EN 60721-3-3
3K3 (-10 ... +55 °C)
Operation at 2/4 kHz, +45 ... +55 °C:
Operation at 8/16 kHz, +40 ... +55 °C:
For operation above +40/+45°C, reduce rated output current
by 2.5 %/°C
Site altitude
0 ... 4000 m amsl
1000 ... 4000 m amsl:
Reduce rated output current by 5 %/1000 m
2000 ... 4000 m amsl: overvoltage category II
Pollution
EN 61800-5-1
Pollution Degree 2
Vibration resistance
(9.81 m/s
2
= 1 g)
Transport
IEC/EN 60721-3-2
2M2
EN 61800-2
2 ... 9 Hz: amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd
5 ... 13.2 Hz: amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
EN 61800-5-1
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 10 m/s
2
(1 g)