5 operation with increased power at a 230 vmains, Operation with increased power at a 230 v mains, Technical data – Lenze 8400 User Manual
Page 54

Technical data
Rated data
Operation with increased power at a 230 V mains
4
54
EDS84ASC552 EN 9.1
4.2.5
Operation with increased power at a 230 V mains
The controller can be operated with increased continuous power (120% P
aN
) on a more
powerful motor. The overload capacity remains constant as if operated with a continuous
power of 100%; the information about the percentage values provided for the overload
phases still refers to rated data of 100%. Typical application cases include drives for units
with quadratic load characteristics such as pumps and fans.
Note!
Operation with increased power is only permitted ...
ƒ
With the rated data provided for the controller.
ƒ
In the stated mains voltage range.
ƒ
At switching frequencies of 2 kHz and 4 kHz.
ƒ
At a max. ambient temperature of 40 °C.
ƒ
With the stated installation types.
ƒ
With the fuses, cable cross-sections, mains chokes and filters required for
this type of operation.
ƒ
After parameterisation acc. to specification (cp. software manual
EDS84AV...)
Basis of the data
Mains
Voltage
Voltage range
Frequency range
U
Lrated
[V]
U
Lrated
[V]
f [Hz]
1/N/PE AC
230
180 - 0 % ... 264 + 0 %
45 - 0 % ... 65 + 0 %
Mains current at I
aN
Apparent output power
Motor power
with external
mains choke
without external
mains choke
U, V, W
4 pol. ASM
Type
I
LR
[A]
I
LR
[A]
S
aR
[kVA]
P
aR
[kW]
E84AVxxx2512
3.6
4.1
0.8
0.37
E84AVxxx3712
5.0
-
1.0
0.55
E84AVxxx5512
6.0
6.4
1.3
0.75
E84AVxxx7512
8.4
-
1.7
1.1
E84AVxxx1122
11.9
14.4
2.4
1.5
E84AVxxx1522
13.7
-
3.0
2.2
E84AVxxx2222
-
-
-
-