EDS84ASC552 EN 9.1
The values of the fuses used may be equal to or fall below the values in the following table:
Branch circuit protection
Fuse [A]
Circuit breaker
Type
with mains
choke
without mains
choke
Type 5kA rms
Type 50kA rms
Rating
E84AVxxx2512
6
6
Schneider Electric:
Multi9 C60
Charact. C
Moeller:
FAZ-C
Charact. C
Siemens:
3RV1742
15 A
E84AVxxx3712
10
10
15 A
E84AVxxx5512
10
10
15 A
E84AVxxx7512
15
15
15 A
E84AVxxx1122
20
20
20 A
E84AVxxx1522
25
25
25 A
E84AVxxx2222
30
30
30 A
E84AVxxx3714
6
6
15 A
E84AVxxx5514
6
6
15 A
E84AVxxx7514
6
6
15 A
E84AVxxx1124
10
10
15 A
E84AVxxx1524
10
10
15 A
E84AVxxx2224
10
10
15 A
E84AVxxx3024xxS
15
15
15 A
E84AVxxx3024xx0
15
15
15 A
E84AVxxx4024
20
20
20 A
E84AVxxx5524
20
20
20 A
E84AVxxx7524
20
25
Siemens:
3RV1742
25 A
E84AVxxx1134
30
40
40 A
E84AVxxx1534
50
-
50 A
E84AVxxx1834
60
60
-
-
-
E84AVxxx2234
60
-
-
E84AVxxx3034
80
-
-
-
-
E84AVxxx3734
100
-
-
-
-
E84AVxxx4534
125
-
-
-
-
Avertissement !
Pour obtenir la certification CSA, les entraînements doivent être destinés à une
utilisation avec des selfs homologuées UL (XPTQ2/8, FOKY2/8) ou certifiées
CSA (XPTQ2, FOKY2), n° de dossier E103521 ou E198787, montées côté
alimentation des équipements.
Ces selfs sont répertoriées sous les 4.2 Caractéristiques assignées ainsi qu’au
chapitre 11.2 Accessoires.