4 operation at a rated mains voltage of 500 v, Operation at a rated mains voltage of 500 v, Technical data – Lenze 8400 User Manual
Page 47
Technical data
Rated data
Operation at a rated mains voltage of 500 V
4
47
EDS84ASC552 EN 9.1
4.2.4
Operation at a rated mains voltage of 500 V
Basis of the data
Mains
Voltage
Voltage range
Frequency range
U
Lrated
[V]
U
Lrated
[V]
f [Hz]
3/PE AC
500
400 - 0 % ... 550 + 0 %
45 - 0 % ... 65 + 0 %
Mains current at I
aN
Apparent output power
Motor power
with external
mains choke
without external
mains choke
U, V, W
4 pol. ASM
Type
I
LR
[A]
I
LR
[A]
S
aR
[kVA]
P
aR
[kW]
E84AVxxx3714
1.1
1.4
0.8
0.37
E84AVxxx5514
1.7
2.2
1.1
0.55
E84AVxxx7514
2.0
2.9
1.5
0.75
E84AVxxx1124
2.6
3.6
2.0
1.1
E84AVxxx1524
3.1
4.4
2.4
1.5
E84AVxxx2224
4.1
5.8
3.5
2.2
E84AVxxx3024xxS
5.6
7.8
4.5
3.0
E84AVxxx3024xx0
5.6
7.8
4.5
3.0
E84AVxxx4024
7.0
10.5
5.9
4.0
E84AVxxx5524
9.6
14.4
8.1
5.5
E84AVxxx7524
12.0
16.0
10.3
7.5
E84AVxxx1134
16.8
23.2
14.7
11.0
E84AVxxx1534
1)
23.2
-
20.0
15.0
E84AVxxx1834
31.0
43.4
26.1
18.5
E84AVxxx2234
1)
36.1
-
31.5
22.0
E84AVxxx3034
1)
46.9
-
40.5
30.0
E84AVxxx3734
1)
58.2
-
50.7
37.0
E84AVxxx4534
1)
69.2
-
60.0
45.0
1)
only with external mains choke