beautypg.com

Nanodac – Carbolite nanodac User Manual

Page 96

background image

nanodac™

MC27 –EN– 1.04

94

AUTOTUNE (Cont.)

AT.R2G

Some load types and process conditions can cause autotune to set an incorrect value for R2G resulting in
an instability in the system after an autotune has completed, In such circumstances, the value of R2G
should be checked, and if it is low (approaching 0.1) a manual entry should be made as follows:
1.

In the Tune menu, set the AT.R2G parameter to ‘No’.

2.

In the PID menu, enter the new R2G value (calculated as described below)

3.

In the Tune menu, enter a value for Low Output, calculated from: Low Output = -High Output x R2G

4.

In the Tune menu, set ‘TuneEn’ On.

R2G CALCULATION

1.

In the Main menu, set the controller to Manual mode

2.

Turn heating on (limited by the value of ‘Output High’ in the

Output menu

) and measure the heating

rate (‘H’ °C/minute).

3.

Allow the process to heat to, say, 10% above the setpoint value then turn the heating off and allow
the temperature to settle.

4.

Turn cooling power on (limited by the value of ‘Output Low’ in the Output menu) and measure the
cooling rate (‘C’ °C/minute) whilst allowing the temperature to fall below the setpoint value.

5.

Calculate the value of R2G from the equation R2G = (H/C) x (Output Low/output High)

Example:

For a measured heating rate (H) of 10°C per min and a measured cooling rate (C) of 25° per minute and
with, Output High = 80% and Output Low = 40%, then R2G = (10/25) x (40/80) = 0.4 x 0.5 = 0.2.











Figure 6.4.5d R2G calculation

Note: This is not a very accurate method as it does not take natural cooling into account. Its main
advantage is that it is simple to achieve.

Heating on

Cooling on

Output Hi

ΔHTemp

Output Lo

ΔCTemp

PV

ΔCTemp = Cooling rate

ΔCTime

ΔCTemp = Heating rate

ΔCTime

ΔCTime

T

empe

ratu

re

O

P

P

ow

er

Time

ΔHTime