beautypg.com

Dlp-700 – ADC Release 3.1 User Manual

Page 65

background image

1152700

Issue 1

February 2001

Section 2 Operations and Maintenance

Page 2-45

© 2000, ADC Telecommunications, Inc.

DLP-700

Page 1 of 1

POWER UP A CELLWORX STN NODE

Summary: This procedure provides instructions for verifying the source

48 Vdc power supply.

1. Turn on the power source that will supply power to the system.

2. Use a multi-tester to measure the DC voltage at the source. When testing, place the positive

probe on the

48 V terminal and the negative probe on the COM or RTN terminal.

3. The measured voltage must be between

42.5 Vdc and

56.5 Vdc at the specified point.

Was voltage within range specified? Note the polarity.

If No, proceed to step 4.

If Yes, continue with step 5.

4. The problem is in the power supply wiring or in the

48 Vdc power supply. Isolate the

problem using local troubleshooting practices and correct as required before installing
power to the system. Repeat procedure after correcting problem.

5. Install fuses or engage the circuit breakers that supply power to the shelf. The front access

cards should illuminate. This can be verified by observing the shelf alarm indicator on the
front door panel. This will only light up if the SC cards are installed and an alarm is
present. Refer to Figure 700-1.

Stop! You have completed this procedure.

DOOR

HINGES

DOOR

LATCH

SHELF

ALARM

INDICATOR

UPPER HEAT BAFFLE/

FIBER MANAGEMENT TRAY

LOWER AIR INTAKE/

CABLE ROUTING TRAY

ESD GROUND JACK

10479-C

Figure 700-1. Cellworx STN Component Identification