5.1.7 Positioning

For the description of parameter P6xx please refer to the instructions BU 0710. (www.nord.com)

5.1.8 Information

Parameter

Setting value / Description / Note

Available with option

P700

Current fault

always visible

0.0 ... 20.9

Actual error present. Further details in Chapter 6 Error messages.

ControlBox:

Descriptions of the individual error numbers can be found in the point Error messages.

ParameterBox: Errors are displayed in plain text, further information can be found in the point Error

messages.

P701

.. - 01

...

.. - 05

Last fault 1...5

always visible

0.0 ... 20.9

This parameter stores the last 5 errors. Further details in Chapter 6 Error messages.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and confirmed
using the ENTER key to read the stored error code.

P702

.. - 01

...

.. - 05

Frequency last error 1...5

always visible

-400.0 ... 400.0 Hz

This parameter stores the output frequency that was being delivered at the time the fault occurred. The
values of the last 5 errors are stored.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and confirmed
using the ENTER key to read the stored error code.

P703

.. - 01

...

.. - 05

Current last error 1...5

always visible

0.0 ... 500.0 A

This parameter stores the output current that was being delivered at the time the fault occurred. The
values of the last 5 errors are stored.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and confirmed
using the ENTER key to read the stored error code.

P704

.. - 01

...

.. - 05

Voltage last error 1...5

always visible

0 ... 500 V

This parameter stores the output voltage that was being delivered at the time the fault occurred. The
values of the last 5 errors are stored.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and confirmed
using the ENTER key to read the stored error code.

P705

.. - 01

...

.. - 05

DC-link voltage last error 1...5

always visible

0 ... 1000 V

This parameter stores the link voltage that was being delivered at the time the error occurred. The
values of the last 5 errors are stored.

The ControlBox must be used to select the corresponding memory location 1-5 (Array), and confirmed
using the ENTER key to read the stored error code.