P102, P400, P103 – NORD Drivesystems BU0700 User Manual
Page 60: P104, P105, P420, P523, 3 minimum configuration of control connections
NORDAC SK 700E Operating Manual
60
Subject to technical alterations
BU 0700 GB-1411
4.3 Minimum configuration of control connections
... with Basic I/O and ControlBox (Option: SK CU1-BSC + SK TU1-CTR)
If the frequency inverter is to be controlled via the digital and analog inputs, this can be implemented immediately in the delivery
condition. Settings are not necessary for the moment.
A prerequisite is the installation of a customer unit, e.g. the Basic I/O as described here.
Minimum circuitry
Basic parameters
If the current setting of the frequency inverter is not known, loading the factory data is recommended P523. The frequency
inverter is parameterised for standard applications in this configuration. If necessary, the following parameters can be modified
(with the Option ControlBox).
P0 - -
Display parameters
_ _ _ _
P1--
Basic parameters
P2- -
Motor data
P4 - -
Control terminals
P5- -
Additional
parameters
P7- -
Information
As
st
a
n
d
a
rd
th
e
a
ct
u
a
l
o
u
tp
u
t
fr
e
q
u
e
n
c
y
is
d
isp
la
ye
d
P102
Acceleration time
0 to 99.99 s
M
o
to
r d
a
ta
Se
e
4
.1
Ba
si
c
se
tt
in
g
s
P400
Funct. analog input
0...10V -frequency-
Operating values display
(or operational)
following mains ON
P103
Deceleration time
0 to 99.99 s
P104
Min. frequency
0Hz to 400Hz
P105
Max. frequency
0.1Hz to 400Hz
P420
Funct. digital input 1
-ON right-
P523
Load factory data
B
a
si
c-
K
u
n
d
e
n
sc
h
n
itt
st
e
lle
X
3
.3
X
3
.2
X
3
.1
01 REL1.1
02 REL1.2
11 VREF 10V
12 AGND /0V
13 AIN1 -
14 AIN1 +
21 DIG IN 1
22 DIG IN 2
23 DIG IN 3
42 VO +15V
Potentiometer, 10kOhm
(Function = P400)
(Range = P104/105)
Switch, ON/OFF
(Function = P420)
B
a
sic cu
st
o
m
e
r un
it