NORDAC SK 700E Operating Manual

66

Subject to technical alterations

BU 0700 GB-1411

Parameter

Setting value / Description / Note

Available in Option

P107 (P)

Brake reaction time

always visible

0 ... 2.50 s

[ 0.00 ]

Electromagnetic brakes have a physically-dependent delayed reaction time when actuated. This can
lead to load drops during lifting applications, as the brake delays in taking over the load.

This reaction time can be taken into account under parameter P107 (Braking control).

Within the adjustable application time, the FI supplies the set absolute minimum frequency (P505) and
so prevents movement against the brake and load drop when stopping.

See also the parameter >Release time< P114

Note:

For the control of electromagnetic braking (especially for lifting operations) an internal relay
should be used,  Function 1, external brake (P434/441).
The minimum absolute frequency (P505) should never be less than 2.0Hz.


Recommendation for applications:

Lifting equipment with brake, without speed feedback


P114 = 0.2...0.3sec.
P107 = 0.2...0.3sec.

P201

…P208 = Motor data

P434 = 1 (ext. brake)
P505 = 2...4Hz

for safe start-up
P112 = 401 (off)
P536 = 2.1 (off)
P537 = 0 (off)
P539 = 2/3 (I

SD

monitoring)


against load drops
P214 = 50...100% (precontrol)

Output
frequency

P107

Brake released

P114
or
P107, when P114 = 0

ON Signal

P505

OFF Signal

Time

Note:

When the brake ventilation time is set (P107 / P114), the brake is only triggered when at
least a ¼ of the nominal magnetising current flows (P209). The static boost P120 is
correspondingly taken into account with values < 100%.