1 technology unit – NORD Drivesystems BU0700 User Manual
Page 22
NORDAC SK 700E Operating Manual
22
Subject to technical alterations
BU 0700 GB-1411
700E
N O R D A C
700E
N O R D A C
3.1 Technology unit
(Technology Unit, Option)
Technology units are snapped onto the inverter externally. They are for the control or parameterisation of the inverter and for
the display of current operating settings..
Technology unit
(SK TU1-...)
Description
Data
ParameterBox
SK TU1-PAR
For text-driven initialisation, parameterisation, configuration
and control of the frequency inverter. Background illuminated
graphic display.
6 languages
Storage of 5 data sets
Help texts
ControlBox
SK TU1-CTR
Used for commissioning, parameterisation, configuration and
control of the frequency inverter.
4-figure, 7-segment
LED display
Potentiometer
SK TU1-POT
For direct control of the drive from the frequency converter.
Potentiometer 0 to 100%
ON / OFF / Reverse button
CANbus module
SK TU1-CAN
This option enables control of the SK 700E via the CANbus
serial port.
Baud rate: 500 KBit/s
Connector: Sub-D 9
Profibus module
SK TU1-PBR
This option enables control of the SK 700E via the Profibus
DP serial port.
Baud rate: 1.5 MBaud
Connector: Sub-D 9
Profibus module
SK TU1-PBR-24V
This option enables control of the SK 700E via the Profibus
DP serial port. Operation requires an external 24V supply.
Baud rate: 12 MBaud
Connector: Sub-D 9
ext. +24V DC supply
RS 232
SK TU1-RS2
This option enables control of the SK 700E via the RS 232
serial port, e.g. using a PC.
Connector: Sub-D 9
CANopen module
SK TU1-CAO
This option enables control of the SK 700E via the CANbus
serial port, using the CANopen protocol
Baud rate: up to 1 MBit/s
Connector: Sub-D 9
DeviceNet module
SK TU1-DEV
This option enables control of the SK 700E via the DeviceNet
serial port using the DeviceNet protocol.
Baud rate: 500 KBit/s
5-pin screw connector
InterBus module
SK TU1-IBS
This option enables control of the SK 700E via the InterBus
serial port.
Baud rate: 500 kBit/s (2Mbit/s)
Connector: 2 x Sub-D 9
AS interface
SK TU3-AS1
Actuator-sensor interface is a bus system for the lower field
bus level, used for simple control tasks.
4 sensors / 2 actuators 5 / 8 pin
screw connector
Mounting
The technology units must be installed as
follows:
1. Switch off the mains voltage,
observe the waiting period.
2.
Remove the blanking cover by
pressing the upper and lower
catches
.
3. Allow the technology unit to engage
audibly by pressing lightly on the
installation surface.
WARNING / NOTE
Modules must not be inserted or removed unless the device is free of voltage. The slots may only be used
for the applicable modules.
Installation of a technology unit separate from the frequency inverter is not possible. It must be connected
directly to the frequency inverter.