NORD Drivesystems BU0700 User Manual
Page 35
3.1 Technology unit
BU 0700 GB-1411
Subject to technical alterations
35
Parameterisation with the ControlBox
The parameterisation of the frequency inverter can be performed in the various operating states. All parameters can always be
changed online. Switching to the parameter mode occurs in different ways depending upon the operating states and the
enabling source.
1. If there is no enable (if necessary, press the STOP key
) via the ControlBox, control terminals or a serial interface, it is
still possible to switch to the parameterisation mode directly from the operating value display with the value keys
or
.
P 0 _ _ / P 7 _ _
2. If an enable is present via the control terminals or a serial interface and the inverter is producing an output frequency, it is
also possible to switch to the parameterisation mode directly from the operating value display using the value keys
or
. P 0 _ _ / P 7 _ _
3. If the inverter is enabled via the ControlBox (START key
), the parameterisation mode can be reached by pressing the
START and ENTER keys
+
simultaneously.
4. Switching back to the control mode is achieved by pressing the START key
.
vector
R
Switching from control to
parameterisation while
the drive is running
(see Point 3)
Select menu group,
display parameter value
One level each time back to
the operating value display
Next menu group or
parameter number
Previous menu group or
parameter number
Switching from
parameterisation to
control (see Point 3)
Parameter set display
Parameterisation of the frequency inverter
To access the parameter section, one of the value keys,
or
must be pressed. The display changes to the menu group
display P 0 _ _ ... P 7 _ _. Once the required menu group has been reached, the ENTER key
must be pressed to access
the individual parameters.
All parameters are arranged in order in the individual menu groups in a continuous scroll pattern. It is therefore possible to scroll
forwards and backwards within this section.
Each parameter has a parameter number P
x x x
. The significance and description of the parameters starts in Chapter 5
"Parameterisation"
Note:
The parameters P542, P701 to 706, P707, P718, P741/742 and P745/746 also have an array level in which further
settings can be made, e.g.:
P_ 0 1
P542
P_ 0 2
0 . 0
0 . 0
Setting:
Value of leading function 1
Setting:
Value of leading function 2
ENTER
ENTER
ENTER
VALUE