11
2.4 Chassis line filter (accessory)
In contrast to the line filter described in Chapter 2.3, the HLD 110 (up
to 110kW) has a UL acceptance for the North American market.
The interference noise suppression level of class A is achieved with
up to a maximum motor cable length of 50m, and class B with motor
cables of up to 25m.
When connecting the line filter, comply with Chapter 2.9 "Wiring
guidelines" and 8.3 "EMC". In particular, ensure that the pulse
frequency is set to the default value (P504 = 4/6kHz). The line filter
should be placed as close to the side of the inverter as possible.
The connection is by means of screw connections on the upper
(mains) and lower (inverter) ends of the filter
Inverter type
SK 700E ...
Filter type
HLD 110 - ...
[V] / [A]
Length
L1
Width
B1
Depth
T
Detail: mounting
Connection
cross-section
Length L2
Width B2
...-151-340-A
...-221-340-A
… 500/8
190
45
75
180
20
4 mm
2
...-301-340-A
...-401-340-A
...-551-340-A
… 500/16
250
45
75
240
20
4 mm
2
...-751-340-A
...-112-340-A
… 500/30
270
55
95
255
30
10 mm
2
...-152-340-A
… 500/42
310
55
95
295
30
10 mm
2
...-182-340-A
… 500/55
250
85
95
235
60
16 mm
2
...-222-340-A
...-302-340-O
… 500/75
270
85
135
255
60
35 mm
2
...-372-340-O
… 500/100
270
95
150
255
65
50 mm
2
...-452-340-O
...-552-340-O
… 500/130
...-752-340-O
… 500/180
380
130
181
365
102
95 mm
2
...-902-340-O
...-113-340-O
… 500/250
450
155
220
435
125
150 mm
2
Design variant, without UL, only noise suppression level A
Bus bar
...-133-340-O
HFD 103-500/300 *
564
300
160
2 x 210
275
8.5mm
...-163-340-O
HFD 103-500/400 *
10.5mm
*) without UL/cUL
All dimensions in mm
L1
L2
L3
L3'
L2'
L1'
L2
L1
B2
T
Netz / LINE
Gerät / LO
AD
B1