6 output choke (accessories), Tb2 b1 l1 l2 – NORD Drivesystems BU0700 User Manual
Page 13
2 Assembly and installation
BU 0700 GB-1411
Subject to technical alterations
13
2.6 Output choke (accessories)
To reduce interference signals from the motor cable or to
compensate for cable capacitance in long motor cables, an
additional output choke can be installed into the inverter
output.
Take care during installation that the pulse frequency of the
frequency inverter is set to 3-6kHz (P504 = 3-6).
These chokes are specified for a maximum supply voltage of
460V at 0-100 Hz.
An output choke should be fitted for cable lengths over
150m/50m (unshielded/shielded). Further details can be found
in Chapter 2.10.4 "Motor cable".
The protection class of the chokes is IP00 and they must
therefore be installed in a control cabinet.
Inverter type
NORDAC
SK 700E
Output choke 3 x 380 - 480V
Length
L1
Width
B1
Depth
T
Detail: mounting
Conn
e
c
tio
n
Type
Permanent
current
Inductance
Length
L2
Width
B2
M
ou
nti
n
g
1.5 kW
SK CO1-460/4-C
4 A
3 x 3.5 mH
104
120
140
75
84
M6
4
2.2 ... 4.0 kW
SK CO1-460/9-C
9.5 A
3 x 2.5 mH
110
155
160
71.5
130
M6
4
5.5 ... 7.5 kW
SK CO1-460/17-C
17 A
3 x 1.2 mH
102
185
201
57.5
170
M8
10
11 ... 15 kW
SK CO1-460/33-C
33 A
3 x 0.6 mH
122
185
201
77.5
170
M8
16
18 ... 30 kW
SK CO1-460/60-C
60 A
3 x 0.33 mH
112
185
210
67
170
M8
35
37 ... 45 kW
SK CO1-460/90-C
90 A
3 x 0.22 mH
144
352
325
94
224
M8
35
55 ... 90 kW SK CO1-460/170-C
170 A
3 x 0.13 mH
200
412
320
125
264
M10
CU bar
bolts
M12
110 … 132 kW SK CO1-460/240-C
240 A
3 x 0.07 mH
225
412
320
145
388
M10
CU bar
bolts
M12
160 kW SK CO1-460/330-C
330 A
3 x 0.03 mH
188
352
268
145
240
M10
CU bar
bolts
M16
All dimensions in [mm]
[mm
2
]
T
B2
B1
L1
L2
1
3
4
2
5
6